Enter your circuit details on the left and click Calculate to get the correct wire gauge per NEC 310.15.

NEC 310.15 Ampacity Reference — Copper Conductors (75°C, 3 conductors in raceway)

AWG / kcmil60°C Ampacity75°C Ampacity90°C AmpacityTypical Use
14 AWG15A20A25AGeneral purpose 15A circuits
12 AWG20A25A30AKitchen circuits, 20A branch
10 AWG30A35A40ADryer, water heater, A/C
8 AWG40A50A55ARange, EV charger (40A)
6 AWG55A65A75AEV charger (50A), sub-panel feed
4 AWG70A85A95ASub-panel, large A/C
3 AWG85A100A110A100A sub-panel feeder
2 AWG95A115A130AService entrance, large feeder
1 AWG110A130A150A150A service
1/0 AWG125A150A170A150–200A feeder
2/0 AWG145A175A195A200A service entrance
3/0 AWG165A200A225A200A main service, large panel
4/0 AWG195A230A260ALarge commercial service
250 kcmil215A255A290ALarge commercial/industrial
350 kcmil260A310A350A400A service entrance
500 kcmil320A380A430ALarge industrial service
Disclaimer: This calculator provides general reference information based on NEC 310.15 and standard derating methods. Always verify wire sizing with your local Authority Having Jurisdiction (AHJ) and the current adopted NEC edition in your jurisdiction. Environmental conditions, specific equipment ratings, and local amendments may affect the required conductor size. The licensed electrician is solely responsible for all code compliance decisions.